产品资料表 -- 西门子LAE10
shutdown is required every 24 hours. The LAE10 is designed for the supervision of oil flames in connection with selenium photocell detectors RAR... Flame safeguards are used primarily in conjunction with the LEC1 burner control on the following applications:
- Dual-supervision of burners: Supervision of the main flame or of the pilot and main flame by two identical or different types of flame detectors
- Supervision of forced draught oil / gas burners: Supervision of the flame with different types of detectors, depending on the operating mode
- Multi-flame supervision: Plants with several burners whose flames must be supervised individually by one or several detectors, whose startup and supervision, however, should or must be carried out centrally and simultaneously by only one burner control
- The flame safeguards can also be used in connection with other types of burner controls provided the given combination and selected circuitry do not impair the burner control’s safety functions
- The flame safeguards are also used as flame indication units in combustion plant with manual startup
技术参数
主要参数 |
主电压 |
AC220V -15%...AC240V +10% |
AC100V -15%...AC1100V +10% |
主频率 |
50...60Hz ±6% |
外部保险丝 |
10A |
功率 |
4.5VA |
端口额定电流 |
2A |
保护等级 |
IP40 |
重量(不含底座) |
305g |
|
环境条件 |
运输环境 |
IEC 60 721-3-2 |
内部条件 |
class 2K2 |
机械条件 |
class 2M2 |
温度范围 |
-20...+60ºC |
湿度 |
<95% |
运行环境 |
IEC 60 721-3-3 |
内部条件 |
class 3K5 |
机械条件 |
class 3M2 |
温度范围 |
-20...+60ºC |
湿度 |
<95% |
不得进水 |
|
技术参数 -- 西门子LAE10
暂无
参数说明 -- 西门子LAE10
暂无
上一件商品:
西门子 QRA2M.C
下一件商品:
西门子RAR9